FNH Air-cooled condenser is an important component in refrigeration equipment. It primarily dissipates the heat released by the refrigerant during the condensation process through air convection, maintaining the normal operation of the refrigeration system. The product can be equipped with different types of condenser fans according to customer requirements to meet various heat dissipation needs.
Technical Parameters Of FNH Type Air-cooled Condenser
Model | Heat exchange capacity (KW) |
Surface (㎡) |
Copper pipe arrangemrnt | Fan Into Travhea(Φmm) |
Into Travhea (Φmm) |
Fluid Outlet (Φmm) |
||||
Qty | ΦFan(mm) | Air volume (m³/h) | Power(W) | Voltage(V) | ||||||
FNH-0.6/2 | 0.6 | 2 | 2x4 | 1 | 200 | 780 | 55 | 220 | 10 | 10 |
FNH-0.9/3 | 0.9 | 3 | 3x4 | 1 | 200 | 780 | 55 | 220 | 10 | 10 |
FNH-1.2/4 | 1.2 | 4 | 3x5 | 1 | 250 | 970 | 80 | 220 | 10 | 10 |
FNH-1.7/6 | 1.7 | 6 | 3x6 | 1 | 300 | 2040 | 1x85 | 220/380 | 10 | 10 |
FNH-2.5/8.0 | 2.5 | 8 | 3x8 | 1 | 300 | 2040 | 1x85 | 220/380 | 10 | 10 |
FNH-4.6/15 | 4.6 | 15 | 4x10 | 1 | 350 | 2700 | 1x180 | 220/380 | 19 | 16 |
FNH-5.4/18 | 5.4 | 18 | 4x10 | 1 | 400 | 4000 | 1x230 | 380 | 19 | 16 |
FNH-6.4/22 | 6.4 | 22 | 5x10 | 1 | 400 | 4000 | 1x230 | 380 | 19 | 16 |
FNH-6.4/22B | 6.4 | 22 | 4x8 | 2 | 350 | 5400 | 2x180 | 380 | 19 | 16 |
FNH-7.3/28 | 7.3 | 28 | 4x9 | 2 | 350 | 5400 | 2x180 | 380 | 19 | 16 |
FNH-9.7/33 | 9.7 | 33 | 4x10 | 2 | 350 | 5400 | 2x180 | 380 | 19 | 16 |
FNH-12.0/41 | 12 | 41 | 4x12 | 2 | 400 | 8000 | 2x230 | 380 | 19 | 16 |
FNH-13.8/50 | 13.8 | 50 | 4x14 | 2 | 400 | 8000 | 2x230 | 380 | 19 | 16 |
FNH-16.7/60 | 16.7 | 58 | 4x14 | 2 | 400 | 8000 | 2x230 | 380 | 22 | 19 |
FNH-20.7/70 | 20.7 | 70 | 4x18 | 4 | 350 | 10800 | 4x180 | 380 | 28 | 22 |
FNH-23.0/80 | 23 | 80 | 4x20 | 4 | 400 | 16000 | 4x230 | 380 | 28 | 22 |
FNH-27.6/100 | 27.6 | 100 | 5x20 | 4 | 400 | 16000 | 4x230 | 380 | 28 | 22 |
FNH-33.3/120 | 33.3 | 120 | 5x24 | 4 | 400 | 16000 | 4x230 | 380 | 32 | 25 |
FNH-39.8/140 | 39.8 | 140 | 5x24 | 4 | 450 | 18800 | 4x280 | 380 | 32 | 25 |
FNH-45.6/160 | 45.6 | 160 | 5x26 | 4 | 450 | 18800 | 4x280 | 380 | 32 | 25 |
FNH-49.9/180 | 49.9 | 180 | 5x26 | 4 | 500 | 26400 | 4x460 | 380 | 32 | 25 |
Appearance And Installation Dimensions of FNH Type Air-cooled Condenser
Model | Overll dimensions | |||||
L | K | H | A | B | W | |
FNH-0.6/2 | 280 | 95 | 240 | 260 | 65 | 140 |
FNH-0.9/3 | 280 | 120 | 240 | 260 | 80 | 165 |
FNH-1.2/4 | 300 | 120 | 290 | 280 | 80 | 175 |
FNH-1.7/6 | 350 | 150 | 340 | 330 | 110 | 235 |
FNH-2.5/8.0 | 450 | 150 | 435 | 420 | 100 | 250 |
FNH-4.6/15 | 485 | 170 | 535 | 455 | 145 | 280 |
FNH-5.4/18 | 520 | 180 | 535 | 490 | 145 | 290 |
FNH-6.4/22 | 600 | 180 | 535 | 570 | 145 | 290 |
FNH-6.4/22B | 875 | 200 | 435 | 845 | 145 | 290 |
FNH-7.3/28 | 875 | 200 | 485 | 845 | 145 | 290 |
FNH-9.7/33 | 935 | 200 | 535 | 905 | 145 | 290 |
FNH-12.0/41 | 935 | 200 | 635 | 905 | 145 | 290 |
FNH-13.8/50 | 935 | 200 | 735 | 905 | 145 | 290 |
FNH-16.2/58 | 1085 | 200 | 735 | 1055 | 145 | 290 |
FNH-20.7/70 | 1085 | 200 | 935 | 1055 | 145 | 290 |
FNH-23.0/80 | 1100 | 220 | 1035 | 1070 | 165 | 310 |
FNH-27.6/100 | 1100 | 220 | 1035 | 1070 | 165 | 310 |
FNH-33.3/120 | 1130 | 220 | 1035 | 1100 | 165 | 310 |
FNH-39.8/140 | 1190 | 220 | 1235 | 1170 | 165 | 320 |
FNH-45.6/160 | 1250 | 220 | 1335 | 1220 | 165 | 320 |
FNH-49.9/180 | 1410 | 220 | 1335 | 1380 | 165 | 320 |